SJ200
2
Inverter
xiii
Terminal Tightening Torque and Wire Size
The wire size range and tightening torque for field wiring terminals are presented in the
tables below.
Wire Connectors
WARNING:
Field wiring connections must be
made by a UL Listed and CSA Certified ring lug
terminal connector sized for the wire gauge being
used. The connector must be fixed using the
crimping tool specified by the connector
manufacturer.
Input
Voltage
Motor Output
Inverter Model
Power Terminal
Wiring Size
Range (AWG)
Torque
kW
HP
ft-lbs
(N-m)
200V
0.2 1/4
SJ200-002NFE(F)2/NFU2
16
0.6
0.8
0.4
1/2
SJ200-004NFE(F)2/NFU2
0.55
3/4
SJ200-005NFE(F)2
0.75
1
SJ200-007NFE(F)2/NFU2
14
0.9
1.2
1.1
1 1/2
SJ200-011NFE(F)2
1.5
2
SJ200-015NFE(F)2/NFU2
12
2.2
3
SJ200-022NFE(F)2/NFU2
10
3.7
5
SJ200-037LFU2
10
5.5
7 1/2
SJ200-055LFU2
10
1.5
2.0
7.5
10
SJ200-075LFU2
8
400V
0.4
1/2
SJ200-004HFE(F)2/HFU2
16
0.9
1.2
0.75
1
SJ200-007HFE(F)2/HFU2
1.5
2
SJ200-015HFE(F)2/HFU2
2.2
3
SJ200-022HFE(F)2/HFU2
3.0
4
SJ200-030HFE(F)2
14
4.0
5
SJ200-040HFE(F)2/HFU2
5.5
7 1/2
SJ200-055HFE(F)2/HFU2
12
1.5
2.0
7.5
10
SJ200-075HFE(F)2/HFU2
Terminal Connector
Wiring Size
Range (AWG)
Torque Range
ft-lbs
(N-m)
Logic and Analog connectors
30—16
0.16—0.19
0.22—0.25
Relay connector
30—14
0.37—0.44
0.5—0.6
Cable
Terminal (ring lug)
Cable support
Summary of Contents for SJ2002 Series
Page 2: ......
Page 46: ......
Page 214: ......
Page 231: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 282: ......
Page 299: ...SJ2002 Inverter Appendix D D 5 L1 L2 L3 PE SJ2002 inverter with book type filter M 3 ...