SJ200
2
Inverter
Appendix B
B–37
B092
Cooling fan control
R/W Selects when the fan is ON
per inverter operation, two
options:
00... Fan is always ON
01... Fan is ON during run,
OFF during stop (5 min.
delay from ON to OFF)
02... Fan is temperature
controlled
10DB
h
04315
0, 1, 2
—
B095
Dynamic braking
control
R/W Three option codes:
00... Disable
01... Enable during RUN only
02... Enable always
10DC
h
04316
0, 1, 2
—
B096
Dynamic braking
activation level
R/W Range is:
330 to 380V (200V class),
660 to 760V (400V class)
10DD
h
04317
330 to
380, 660
to 760
1 V
B130
Over-voltage
LADSTOP enable
R/W Pauses deceleration ramp
when DC bus voltage rises
above threshold level, in order
to avoid over-voltage trip.
Two option codes:
00... Disable
01... Enable
10F5h
04341
0, 1
—
B131
Over-voltage
LADSTOP level
R/W Sets the threshold level for
over-voltage LADSTOP.
When the DC bus voltage is
above the threshold value, the
inverter stops deceleration
until the DC bus voltage is
less than the threshold setting
again.
10F6h
04342
330 to
390,
660 to
780
1 V
B140
Over-current trip
suppression
R/W Two option codes:
00... Disable
01... Enable
10F7h
04343
0, 1
—
B150
Carrier mode (not
accessible to ModBus)
—
Automatically reduces the
carrier frequency as the
ambient temperature
increases.
Two option codes:
00... Disable
01... Enable
10F8h
04344
0, 1
—
“B” Group Fine Tuning Functions
Func.
Code
Name
R/W
Description
Network Data
Register
Range
Res.
hex
dec.