Using Intelligent Input Terminals
Oper
ations
and Monitor
ing
4–14
While using the multi-speed capability, you can monitor the present frequency with
monitor function D001 during each segment of a multi-speed operation.
NOTE:
When using the Multi-speed Select settings CF1 to CF4, do not display parame-
ter F001 or change the value of F001 while the inverter is in Run Mode (motor running).
If it is necessary to check the value of F001 during Run Mode, please monitor D001
instead of F001.
There are two ways to program the speeds into the registers A020 to A035:
1.
Standard keypad programming:
a.
Select each parameter A020 to A035.
b.
Press the
key to view the parameter value.
c.
Use the
and
keys to edit the value.
d.
Use the
key to save the data to memory.
Option
Code
Terminal
Symbol
Function Name
Input
State
Description
02
CF1
Multi-speed Select,
Bit 0 (LSB)
ON
Binary encoded speed select, Bit 0, logical 1
OFF
Binary encoded speed select, Bit 0, logical 0
03
CF2
Multi-speed Select,
Bit 1
ON
Binary encoded speed select, Bit 1, logical 1
OFF
Binary encoded speed select, Bit 1, logical 0
04
CF3
Multi-speed Select,
Bit 2
ON
Binary encoded speed select, Bit 2, logical 1
OFF
Binary encoded speed select, Bit 2, logical 0
05
CF4
Multi-speed Select,
Bit 3 (MSB)
ON
Binary encoded speed select, Bit 3, logical 1
OFF
Binary encoded speed select, Bit 3, logical 0
Valid for inputs:
C001, C002, C003, C004,
C005, C006
Required settings:
F001, A001 = 02,
A020 to A035
Notes:
•
When programming the multi-speed settings, be
sure to press the Store key each time and then set
the next multi-speed setting. Note that when the key
is not pressed, no data will be set.
•
When a multi-speed setting more than 50Hz(60Hz)
is to be set, it is necessary to program the maximum
frequency A004 high enough to allow that speed.
1
2
3
4
5
6
L
PCS
Example (some CF inputs require input
configuration; some are default inputs—see
page
3–45
):
See I/O specs on page
4–6
.
CF2
CF3
CF4
CF1
(LSB)
(MSB)
FUNC.
1
2
STR