2 Optional accessories
Deodorising filter
SMGB0137 rev.0 - 05/2021
32
2.6.2 For RCD-FSR indoor units: F-90MD-K1 and F-160MD-K1 (Antibacterial long life air
filter)
352
a
40
40
P
68
49
60
417
300
8
630
10
Indoor unit
Antibacterial
long life air filter
Filter box (option)
Ceiling
Air panel
Long life air filter
Attached with
optional Air panel
Air inlet
flat grille
Filter holder
(*1)
Installation
height
Min.
Paper
frame
Filter
media
Model/Air flow direction
Air
?
N O T E
(*1)
Insert the antibacterial long life air filter into the filter box, the fix it with the
filter holder
Air flow chart
Applicable Indoor unit
RCD-(0.8-3.0)FSR
RCD-(4.0-6.0)FSR
20
10
30
40
0
20
40
B:F-160MD-K1
A:F-90MD-K1
A
B
Air volume (m
3
/min)
Pressure Loss (Pa)
Dust collection efficiency
%
65 (Gravimetric method (*1))
Air flow
m
3
/min.
19.5
32.5
Initial pressure Loss
Pa (mmAq)
17.0
20.5
End pressure Loss
Pa (mmAq)
55.9
62.8
Colour (Filter/frame)
White / Brown
Life period
8 years (with 2500 hours maintenance)
Cleaning
Not available
Accessory
Installation manual
Weight
kg
0.9
0.8 x 2
Performance
Avoids the multiplication of bacteria and
mould
Filter material
Antibacterial fibre
Synthetic fibre Non-woven fabric
2.7
Deodorising filter
2.7.1 For RCI-FSR indoor units: F-71L-D1 and F-160L-D1
The dimensions of the deodorising filter are indicated in the following figure.
Remember that the filter thickness depends on the model.
588
544
588
544
AIR FLOW
F-160L-D
1
a
2 pieces
(reinforcement)
Model
Filter
Aluminium
frame
Air
Air flow direction
Model
Dimension
F-71L-D1
F-160L-D1
a
25
45