5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
155
5
Item
Optional function
Individual
Setting
Settings
Setting conditions
Description
r3
Setback
temperature
compensation
×
0.5
0.5 ºC
This setting is the temperature
differential value to adjust the
setting temperature during Setback
operation.
1.0
1.0 ºC
1.5
1.5 ºC
2.0
2.0 ºC
2.5
2.5 ºC
3.0
3.0 ºC
3.5
3.5 ºC
4.0
4.0 ºC
4.5
4.5 ºC
5.0
5.0 ºC
5.5
5.5 ºC
r4
Not used
-
00
-
Use at 00 conditions
01
r5
Not used
-
00
-
Use at 00 conditions
01
r6
Not used
-
00
-
Use at 00 conditions
01
r7
Not used
-
00
-
Use at 00 conditions
01
r8
Not used
-
00
-
Use at 00 conditions
01
r9
Not used
-
01
-
Use at 00 conditions
02
rA
Not used
-
00-07
-
Use at 00 conditions
rb
Not used
-
00-12
-
Use at 00 conditions
S1
Not used
-
00
-
Use at 00 conditions
01
S2
Not used
-
00
-
Use at 00 conditions
01
S3
Not used
00
-
Use at 00 conditions
01
S4
Not used
00
-
Use at 00 conditions
01
S5
Not used
00
-
Use at 00 conditions
01
S6
Not used
00
-
Use at 00 conditions
01
02
S7
Not used
00-07
-
Use at 00 conditions
S8
Not used
00-15
-
Use at 00 conditions
?
N O T E
•
T
he changes to the optional function settings must be done after 3 minutes have passed since start-up.
• It is recommended to keep track of the changes made to optional function settings, for further reference.
• The available optional settings are different depending on the indoor and outdoor unit models. Check the technical documentation of
the indoor and outdoor units to ensure whether the optional settings are available for these units.
• The above optional functions marked with an “X” at the individual setting can change the condition only when “All Rooms” is set.