5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
121
5
Element
Optional function
Individual
setting
Settings
Setting conditions
Description
Pb
Not used
-
00
-
Use at 00 conditions
01
PC
Not used
-
00
-
Use at 00 conditions
01
q1
Not used
-
00
-
Use at 00 conditions
01
q2
Not used
-
-
-
Not used
q3
Not used
-
-
-
Not used
q4
Not used
-
-
-
Not used
q5
Not used
-
-
-
Not used
q6
Not used
-
00
-
Use at 00 conditions
01
q7
Not used
-
00
-
Use at 00 conditions
01
q8
Not used
-
00
-
Use at 00 conditions
01
q9
Not used
-
00
-
Use at 00 conditions
01
qA
Not used
-
00
-
Use at 00 conditions
01
qb
Operation mode with
setback
X
00
Disabled
Operation modes in which
setback operation is activated to
keep a minimum comfort in the
room while it is not occupied.
01
Cooling
02
Heating
03
Cooling/Heating
qC
Temperature differential
for the setback function
X
00
2.0 ºC
Target temperatures for both
cooling and heating operation
are determined versus a
temperature to start setback
operation (rE, rF)
Target temperature calculation:
Target temperature in cooling
mode: rF - qC (°C)
Target temperature in heating
mode: rE + qC (°C)
01
3.0 ºC
02
4.0 ºC
03
5.0 ºC
04
1.0 ºC
qd
Minimum stop time of
setback
X
00
10 minutes
To avoid the frequent activation
of setback operation, a minimum
off-time shall pass from the
end of setback operation until
the beginning of the following
setback operation.
Even if room temperature
reaches the setpoint to start
setback operation, setback
operation does not start until the
minimum off-time has expired.
01
20 minutes
02
30 minutes
03
40 minutes
04
50 minutes
05
60 minutes
06
70 minutes
07
80 minutes
08
90 minutes
09
100 minutes
10
110 minutes
11
120 minutes
qE
Setback mode
X
00
Always
When selecting “01: Input”,
it is necessary to set up one
input contact (i1 or i2) with
the setback function “09”. This
operation has to be done in the
input/output setting menu of the
remote controller.
When selecting “02: Schedule”
or “03: Manual”, additional
settings are required.
01
Input
02
Schedule
03
Manual
qF
Operation state after the
end of setback operation
X
00
Stop
Operation state to switch
to upon the end of setback
duration.
01
Run
02
Operation state before the beginning
of setback