5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
144
Item
Optional function
Individual
Setting
Settings
Setting conditions
Description
C6
Increase of fan
speed at heating
Thermo-OFF
(Not available for
models KPI-E4 and
KPI-X4E)
○
00
Function disabled
(factory setting)
This function is used to increase
the fan speed when the thermostat
reaches the set temperature in
heating according to the setting of
function C5.
01
Function enabled
C7
Cancellation of
forced compressor
operation for at least
3 minutes
○
00
Function disabled
(factory setting)
This function is available depending
on the setting of function b3.
01
Function enabled
(Compressor operation during
3 minutes is no longer forced)
Only for KPI-E4E
and KPI-X4E
CO
2
sensor enabled
00
Sensor non enabled
(factory setting)
Via 7-segments display set the
option
Ct
(00: ON/OFF Sensor
(Default); 01: 4-20mA 02: 0-10V).
01
Sensor enabled/activated
C8
Control by the
temperature sensor
of the remote control
switch
?
N O T E
The remote control
switch
shall
be
installed in a proper
place for the correct
detection of room
temperature by its
temperature sensor.
○
00
Control by the air inlet sensor of
indoor units (factory setting)
This function specifies the
temperature sensor to be used as
control sensor by the indoor unit.
01
Control by the temperature sensor
of the remote control switch
02
Control by the average value of
the air inlet sensor of indoor units
and the temperature sensor of the
remote control switch
(Air inlet + Remote control switch)/2
Control sensor when
a remote sensor is
connected to the
THM4 connector in
the indoor unit PCB
?
N O T E
The remote sensor
shall be installed in a
proper place for the
correct detection of
room temperature.
Model
RPF(I)-FSN2E
○
00, 01, 02
When a remote sensor is connected
to THM4, this remote sensor is used
as control sensor, whichever the
setting for C8
(factory setting C8=00)
Control sensor when
a remote sensor is
connected to the
THM4 connector in
the indoor unit PCB
?
N O T E
The remote sensor
shall be installed in a
proper place for the
correct detection of
room temperature.
Models
RCI-FSR
RCIM-FSRE
RCD-FSR
RPC-FSR
RPI(L/H)-FSRE
RPI-FSN3E(P)E(-f)
RPK-FSR(H)M
○
00, 02
Air temperature control using
the average value of the air inlet
thermistor and the remote sensor
(factory setting C8=00)
(Air inlet + Remote sensor)/2
01
Air temperature control using the
remote sensor