5 Optional functions
Optional functions through Remote control
SMGB0137 rev.0 - 05/2021
129
5
CE – Stop of indoor unit fan during heating Thermo-OFF conditions
This function is useful to avoid the perception of cold draughts.
When “CE=01”: Fan stop operation in thermo-off conditions when using the PC-ARFP1E sensor, “C8=01” must be set in
this case. The fan will not be turned on when the indoor unit is switched on in Thermo-OFF conditions.
Indoor unit will use the PC-ARFP1E Remote Control temperature sensor to monitor the room temperature when fan is
stopped (heating Thermo-OFF fan stop sequence). The Remote Control Switch shall be installed in a proper place for the
correct detection of room temperature by its temperature sensor.
Control by Remote Temperature Sensor not permitted.
Indoor unit Operation
(Cool Mode)
Tset+1ºC
Tset-1ºC
PC-ARFP1E
HEAT Thermo-ON
Fan Operation
Fan Stop in Heating Thermo-OFF even at start-up
(Compressor ON)
TH-ON conditions
TH-OFF conditions
OFF
OFF
ON
Tset
ON
Fan Stop in Thermo-OFF after unit start-up
?
N O T E
• These functions are only available when using the Remote Control Sensor (in PC-ARFP1E)
• When using CE function:
- “C8=00”: this setting is not permitted
- “C8=02”: this setting is not recommended since it may cause that comfort conditions are never reached (C8 set at 02 means that
unit control is carried out with the average value of the Remote Control Sensor and the air inlet sensor of the indoor unit)
• In case that Automatic louver is set, the louver will keep operating in both Thermo-ON and Thermo-OFF conditions
CF – Change of louver swing angle
This function is useful when the louver swing angle (air discharge angle) must be changed.
Air discharge
angle
Setting condition
Louver swing angle (Air discharge angle)
Purpose
00
7 steps
Standard Operation
01
5 steps
Cold draft Prevention
02
5 steps (*)
For High Ceiling
?
N O T E
(*) Not used for RPK-FSR(H)M