5 Optional functions
Indoor units input and output signals
SMGB0137 rev.0 - 05/2021
95
5
Indication
Connections
Output 1
Output 2
Output 3
Component
Manufacturer or specifications
Remarks
Auxiliary relay (X2)
Reduced power relay model OMRON:
MY1F or equivalent
Voltage between the relay terminals
12 V DC, 75 mA
Contact (SS1) (x1) (example)
Manual type
Voltage between the contactor terminals
230 V, 5 mA
3-pin connector cable
Optional part PCC-1A
(capable of connecting the connector
(JST XHP-3))
Five cables with connectors in one group
Cable (control)
Voltage: 12 VDC
0.5 mm
2
Cable (power)
Voltage: 230 V
2.0 mm
2
Recommendations for wiring installation
•
Keep the CN3 connector cables as short as possible.
•
Try not to pull on the cable along the power line. The cables should be laid separately at a distance of over 30 cm.
Cable crossing is feasible.
•
Where the cable along the power line is pulled, insert the cables through a metal pipe, earth one end of the pipe and
install a safety device such as an earth leakage breaker or smoke detector.
•
It is recommended to install safety devices such as an electric leakage breaker, etc, (because this is unattended
function).