7 Servicing
RPI-(8.0-20.0)FSN3(P)E(-f) - Ducted indoor unit
SMGB0137 rev.0 - 05/2021
238
For RPI-(16.0/20.0)FSN3PE(-f)
1
The servicing of these units can be carried out either by
the fan motor side cover or by the cycle service cover.
Access to the drain pan through any of these covers
and clean it in order to guarantee a correct operation.
Drain pan
7.6.6
Fan removal
For RPI-(8.0/10.0)FSN3E(-f)
1
Remove all screws -A- from the lower cover of the unit
and separate it.
2
Remove the electrical box cover as indicated in chapter
“7.6.1 Removal of the electrical box cover”
.
3
Disconnect the fan motor.
?
N O T E
To disconnect and remove the fan motor, previously see the
chapter corresponding to the wiring diagrams in this Manual.
4
Remove the drain pan as indicated in chapter
“7.6.5 Removal of the drain pan”
5
Remove the wiring -A- from the electrical box and
release it from the support -B-.
6
Remove the screws -C- on both sides of the fan.
!
C A U T I O N
• Make sure the fan can be removed correctly, without the risk
of injuring anyone in the surrounding area.
•
The fan is heavy. Request the assistance of two operators to
hold the fan while it is being removed.