5 Optional functions
Complementary systems
SMGB0137 rev.0 - 05/2021
171
5
5.3 Complementary systems
5.3.1
KPI and DX-Interface
5.3.1.1
7-segments display main menus
F 2 8
.
8
.
F 1 8
.
8
.
8
.
8
.
8
.
8
.
Manual overriding
Check data menu
Configuration menu
Push
PSW1+PSW2+PSW3
for 3 seconds
Push
PSW1
for 3 seconds
Push
PSW1+PSW2
for 3 seconds
To come back to current status, push PSW1 for 3 seconds
Check data menu functions
Push PSW1 during 3 seconds in order to activate the check data menu, push PSW2 tot move up or PSW3 to move down.
Push PSW1 during 3 seconds to return.
Check data:
Code
display
Data
display
Description
Detector
Check
function
Application unit
Remarks
KPI-E4E
KPI-X4E
DX-
Interface
t1
Air inlet DX Coil (Tx)
PCB2 THM1
(ºC)
-
O
(○)
Tin DX Coil
t2
Air outlet DX Coil (Tx’)
PCB2 THM2
(ºC)
-
O
(○)
Tout DX Coil
F1
Fan 1 (0-83)
CN5-2
(%)
O
O
(○)
s1
Fan 1 Tach
CN5-1
(Hz)
O
O
(○)
f2
88
Fan 2 (0-83)
CN6-2
(%)
O
O
(○)
s2
Fan 2 Tach
CN6-1
(Hz)
O
O
(○)
1
Duty 0-10v
CN3-2
(v)
-
-
(○)
(or 0-5v)
2
Duty 4-20mA
CN2-2
(mA)
-
-
(○)
00
Soft PCB 1
H-LINK
(Soft number)
O
O
O
(H-0XXX)
0
.
0
.
Soft PCB 2
H-LINK
(Soft number)
O
O
O
(H-0XXX)
(○) Optional