No.
Event
Items to be checked
Action
6 Even if this system is
in Run command,
the Air conditioner
does not run.
Check that there is no error
between the Computer and this
system connection.
Check if the LAN cable is wired correctly and if
the HUB and this system power is turned ON.
Check if the Alarms 60, 61, 64
and 65 are ON.
A communication error has occurred in H-LINK.
Check if the power of the Air conditioner is not
OFF, check H-LINK wiring and transmission
status.
Is the air conditioning unit in
[Stop] or in [Emergency Stop]
mode depending on the External
input of this unit?
Deactivate the External Input Signal.
Is the RC group correctly
registered?
RC groups must be allocated to one group
number between
“1-160”. If “O” is shown, allocate one number
from “1-160”.
Did the connection of the RC
change such as in
the removal of the RC?
To modify the connection to the RC, execute it
while the power to the AC is OFF.
If the modification is performed while the AC
is ON, turn the power OFF once, then turn the
power back ON.
Then click [Check connection] in [Settings] >
[Unit register] of the management software.
Is Stop Signal depending on the
External input in the Indoor unit
is ON?
The halt depending on the External Input Signal
inputed in the Indoor unit is taking priority.
Deactivate the External Input Signal.
Is there a time setting
discrepancy between the Unit
and the computer?
*
The displayed time in the
lower right hand corner of the
applications user interface
should match the current time on
the PC.
Set the time of this unit following the
Preparation for Setup of this manual [the item
of (9) of
1
Power supply (page 11)].
7
Even operating from
this system,
it will stop after a
certain time.
Did the connection of the RC
change, such as in the removal of
the RC?
To modify the connection to the RC, execute it
while the power to the AC is OFF.
If the modification is performed while the AC
is ON, turn the power OFF once, then turn the
power back ON.
Then click [Settings] > [Unit register] of the
management application and recheck the
connection.
8 Certain units are not
operating even in [On
all].
Does [On all] have any effect on
the unit?
Select the item for [All prohibited] in Control
Panels as [None] or [OFF].
9 Certain units are not
stopping even in [Off
all].
Does [Off all] have any effect on
the unit?
Select the item for [All prohibited] in Control
Panels as [None] or [ON].