Alarm code
55
Inverter failure.
•
The RUN indicator flashes and the ALARM indication is displayed on the remote control switch.
•
The unit no., the alarm code and the unit code are alternatively displayed in the temperature setting section and the unit
no. and alarm code are displayed on the outdoor unit's PCB1 display.
* This alarm is indicated when the following phenomenon occurs three times in thirty minutes (retry operation is carried
up to the second time the anomaly occurs).
The actual frequency from PCB2 is less than 10 Hz (after the Inverter frequency output from PCB1).
Activation condition: this alarm is indicated when PCB2 is not performed normally.
Yes
Turn off power (LED201 OFF)
and restart operation.
Is alarm code “55” indicated
again?
No
PCB2 is normal.
Check the noise filter. *1)
Replace the PCB2.
No
PCB1: Control PCB in Outdoor Unit
PCB2: Inverter PCB
*1): When the unit is applied the excessive surge current due to lightning or other causes, alarm code "55" or Inverter
stoppage code (IT) "11" is indicated and the unit cannot be operated. In this case, check to ensure the surge absorver
(SA) in the noise filter (NF1, NF2). The surge absorver may be damaged if the inner surface of the SA is black. If so, replace
the surge absorver.
If the inside of the surge absorver is normal, turn OFF the power supply and wait for LED201 (red) of PCB2 OFF
(approximately 5 minutes) and turn ON power supply again.
Positioning of surge absorver:
Lot
SP-226-1
250VAC/30A
OKAYA
LFB-14930-3MA
E
NF1
NF2
SA
SA
SA: Surge absorver.
8 Troubleshooting
226
SMGB0065 rev. 1 - 12/2010