Alarm code
35
Incorrect indoor unit number setting.
•
The RUN indicator flashes and the ALARM indication is displayed on the remote control switch.
•
The unit no., the alarm code and the unit code are alternatively displayed in the temperature setting section and the unit
no. and alarm code are displayed on the outdoor unit's PCB1 display.
* This alarm is indicated 5 minutes after power is supplied to the outdoor unit when the indoor unit number connected
to the outdoor unit is duplicated by the DSW and RSW setting.
N O T E
In the case of H-LINK systems, this alarm code is indicated when DSW1 and RSW1 of PCB1 of the outdoor unit
and DSW5 and RSW2 of the PCB of the indoor unit are incorrectly set.
In this case, set them properly after turning OFF the main power switch and turn ON again the main power switch.
When the setting of the refrigerant cycle number of the outdoor unit (H-LINK II) and one of the outdoor unit (H-
LINK) is duplicated, alarm code "35" can be ON and OFF repeatedly.
PCB1: Control PCB for the outdoor unit.