Demand stoppage (Control function number 3)
•
When the input terminals for the outdoor unit PCB1 demand stoppage are short-circuited, the compressor or
compressors will be stopped. In this case, the indoor units will be under Thermo-OFF condition. In cooling mode: air
flow setting, heating mode: Lo setting.
•
Short-circuit terminals 1 and 2 (input 3) of CN18 to set the stoppage demand.
•
The stoppage code is number 10. By disconnecting the demand switch contact, restarting is available.
N O T E
•
In case the control demand (ON/OFF) is completed, it is recommended that the control (ON/OFF) time
configuration is set according to the heat load recommendation. Also set the demand control time once in 30
minutes, the minimum to save energy.
X1
1
2
1
2
3
CN18
SS3
X1
a
b
c
d
a
3-pin connector
b
Outdoor unit PCB1
c
Control circuit
d
Power source
X1
Auxiliary relay
SS3
Demand stoppage switch
¿
Outdoor unit fan motor start/stop (Control function number 4)
•
When the outdoor unit PCB1 input terminals for the outdoor unit fan motor are short-circuited during the compressor
stoppage, all the outdoor unit fans will be operating at maximum speed. However, if the compressor is activated via the
compressor operation, the fan operation changes to normal condition. If the input terminals are open, the fans are
stopped. This function protects the outdoor units in case they are covered in snow.
•
Short-circuit terminals 1 and 2 (input 3) of CN18 to set the outdoor unit fan motor start/stop.
•
This function is only available when the compressor is stopped. Therefore, if the input signal is mistakenly sent during
a normal cooling or heating operation, this function will not be available.
X1
1
2
1
2
3
CN18
SS3
X1
a
b
c
d
a
3-pin connector
b
Outdoor unit PCB1
c
Control circuit
d
Power source
X1
Auxiliary relay
SS3
Snow sensor switch
6 Optional functions
118
SMGB0065 rev. 1 - 12/2010