12.9 Service and maintenance table
No.
Check item
Action
Judgement
1
Is the service space sufficient?
Yes
No
2
Is there a short circuit in the discharge air?
Yes
No
3
Any heat influence?
Yes
No
4
Is the earth wire connected?
Yes
No
5
Refrigerant pipe
Correct
Incorrect
6
Fixing of units
Correct
Incorrect
7
Are the internal and external surfaces
damaged?
Yes
No
8
Are the screws and bolts tightened?
Tighten if loose.
Tightened
Not
tightened
9
Are the terminal screws tightened?
Tighten the screws on the terminals with a
Philips screwdriver.
Tightened
Not
tightened
10
Are the compressor terminals tightened?
Push all the terminals.
Push
Not
push
11
Insulation resistance
Measure the insulation resistance with a
multimeter.
Fan and compressor:
Motor: greater than 3 M
Ω
.
Others: greater than 3 M
Ω
.
Correct
Incorrect
12
Are there drainage problems in the water
flow?
Check the smoth flow with a little water.
Correct
Incorrect
13
Is there leakage in the compressor?
Check there is no leakage.
Correct
Incorrect
14
Is there leakage in the outdoor heat
exchanger?
Check there is no leakage.
Correct
Incorrect
15
Is there leakage in the indoor heat
exchanger?
Check there is no leakage.
Correct
Incorrect
16
Is there leakage in the 4-way valves?
Check there is no leakage.
Correct
Incorrect
17
Is there leakage in the check valve?
Check there is no leakage.
Correct
Incorrect
18
Is there leakage in the accumulator?
Check there is no leakage.
Correct
Incorrect
19
Is there leakage in the strainer?
Check there is no leakage.
Correct
Incorrect
20
Is there leakage in the expansion valve?
Check there is no leakage.
Correct
Incorrect
21
Is there leakage in the piping?
Check there is no leakage.
Correct
Incorrect
22
Check the direction of the fans
See the air flow volume.
Correct
Incorrect
23
Check the voltage of each phase
Greater than 220 V.
Correct
Incorrect
24
Vibrations and noise
Check the compressor, the piping, the fan,
etc.
Correct
Incorrect
25
Activation of the operation modes
Activate the COOL switch, the HEAT switch,
the STOP switch and the TEMP switch.
Correct
Incorrect
26
Cut-out of the high pressure switch
Check the current activation valve.
Correct
Incorrect
27
Activate the drain-up mechanism
Check it is activated during cooling mode.
Correct
Incorrect
28
Indoor inlet air temperature DB/WB
—
(°C) DB
(°C) WB
29
Indoor outlet air temperature DB/WB
—
(°C) DB
(°C) WB
30
Outdoor inlet air temperature DB/WB
—
(°C) DB
(°C) WB
31
Outdoor outlet air temperature DB/WB
—
(°C) DB
(°C) WB
32
High pressure switch
—
MPaG
33
Low pressure switch
—
MPaG
12 Maintenance notes
359
SMGB0065 rev. 1 - 12/2010