Alarm code
5C
Abnormal fan controller sensor.
* Activation conditions:
This alarm is indicated when the following conditions occur.
•
After starting the fan motor operation, the fan controller current does not increase over 1.5 A.
•
Before starting the fan motor operation, the fan controller peak current does not increase over 4 A.
Check the fan motor.
Restart operation.
Abnormal
Faulty fan controller
and replace
fan controller. *1)
Faulty fan controller
and replace
fan controller. *1)
Fan motor stops
immediately.
Fan motor is not operated.
How is fan motor
operation when
restarted?
Is the fan motor coil
normal?
Normall
*1): Carry out the electrical discharge when fan controller is checked or replaced, refer to:
, see on page 267
.
8 Troubleshooting