![Hitachi FSXN Series Service Manual Download Page 197](http://html.mh-extra.com/html/hitachi/fsxn-series/fsxn-series_service-manual_139460197.webp)
Alarm code
0b
Incorrect outdoor unit adress setting.
•
The RUN indicator flashes and the ALARM indication is displayed on the remote control switch.
•
The unit no., the alarm code and the unit code are alternatively displayed in the temperature setting section and the unit
no. and alarm code are displayed on the outdoor unit's PCB1 display.
No
Yes
No
Yes
No
Yes
Is DSW6 setting for
outdoor unit B and C correct?
(DSW6: outdoor unit address setting)
Set DSW6 correctly for
outdoor unit B and C and
reset the power supply.
Are 4 (four) or more
outdoor units connected to
O.U.~O.U. transmission terminal?
Correctly connect operating line
between outdoor unit and outdoor
unit and reset the power supply.
Correctly connect wiring between
outdoor unit and outdoor unit and
reset the power supply.
Is operating line between outdoor
unit and outdoor unit connected
INCORRECTLY?
Abnormality of PCB1 in
outdoor unit A
Unit A
(Main)
Unit B
(Sub)
Unit C
(Sub)
Outdoor Unit
PCB1: Control PCB in Outdoor Unit
O.U.: Outdoor Unit
(Sub): Secondary unit(s).
8 Troubleshooting