Discharge temperature increase protection control
The discharge temperature increase protection control is carried out to protect the compressor motor coil from a discharge
pressure increase during an anomaly.
N O T E
1 In the case of base unit combinations, the control of the figure is carried out for the whole outdoor units to be
connected.
2 In order to carry out this control, the discharge temperature of each outdoor unit is calculated and the maximum
value is used.
Td: discharge gas temperature sensor detected value.
A. Normal operation.
B. Forced decrease in frequency (1.0 Hz/s).
C. Not allowing frequency increases (only frequency decreases are
allowed).
D. Abnormal stoppage (cause of the stoppage d1-15).
(1)
For 5 seconds.
(2)
For 10 minutes.
¿
Suction pressure protection control
The suction pressure protection control is carried out to protect the compressor from a transitory decrease in suction
pressure.
N O T E
1 In the case of base unit combinations, the control of the figure is carried out for the whole outdoor units to be
connected.
2 In order to carry out this control, the suction temperature of each outdoor unit is calculated and the maximum
value is used.
Ps: suction pressure sensor detected value.
A. Normal operation.
B. Forced decrease in frequency (0.25 Hz/s).
C. Not allowing frequency increases (only frequency decreases are
allowed).
D. Abnormal stoppage (cause of the stoppage d1-15).
(1)
For 12 minutes.
¿
Degeneration control
The degeneration control is carried out to modify the protection control range. Prevents frequent ON/OFF caused by alarm
when retry stoppage by the abnormal control occurs.
Protection control ratio:
(1) Pressure ratio decrease protection control.
(2) Discharge pressure increase protection control.
(3) Inverter overcurrent protection control.