Alarm code
02
Activation of the outdoor unit protection device.
•
The RUN indicator flashes and the ALARM indication is displayed on the remote control switch.
•
The unit no., the alarm code and the unit code are alternatively displayed in the temperature setting section and the unit
no. and alarm code are displayed on the outdoor unit's PCB1 display.
* This alarm is indicated when one of the safety devices is activated during the compressor running.
Does CMC1 ON
when starting?
Does CMC1 turn
ON for more than
3 seconds?
Yes
No
Normal PCB1
Is the voltage between PCN2 #1
and faston terminal "
" on
PCB1 220V or 240V during LED ON?
Yes
Is the protective device
still operating?
No continuity between #1
and #3 of PCN2, PCN16
on PCB1.
Is PCN2 or PCN16
on PCB1 loosened?
Yes
Yes
Yes
Check activation of the following safety devices. Remove the cause after checking.
High Pressure Switch (PSH): 4.15MPa
Faulty PCB1
Faulty PCB1
Restart after connecting
PCN2 or PCN16 on
PCB1 correctly.
Check Wiring Connection
Except for PCB1
No (No Voltage)
No (No Looseness)
No
PCB1: Control PCB in Outdoor Unit
Check the following elements:
Connector for CMC1
Faston terminal *
Connector for the protection device
PCN3
400V 50Hz
N1
PCN2 or PCN16
Model
High pressure switch (connector no.)
PSH1 (PCN2)
PSH2 (PCN16)
RAS-(8-12)FSXN
O
–
RAS-(14-18)FSXN
O
O
8 Troubleshooting
171
SMGB0065 rev. 1 - 12/2010