Converted frequency of constant speed compressor
Outdoor unit capacity (HP)
Power supply frequency (Hz)
MC2
14,16
50
18
60
N O T E
The maximum frequency for the 8 to 18 HP outdoor units is indicated as: Inverter fre converted frequency
of constant speed compressor.
6.3.3 Cancellation of the outdoor ambient temperature limit
•
Press PSW3 and select the setting condition “1” to “3” at the cancellation of outdoor ambient temperature limit of
G5
.
Then this function can be set.
•
The heating operation is continued under a high outdoor temperature or the cooling operation is continued under a low
temperature.
•
The limitation of the outdoor unit temperature area for heating mode is shown in the picture.
Setting condition
Operation mode for cancellation
1
Heating
2
Cooling
3
Heating/Cooling
Heating operation
A
Indoor suction air temperature
B
Operation stoppage area
C
Outdoor temperature
The limitation of the permissible outdoor temperature area in
heating operation (factory-set) as shown in the right figure is
canceled.
Cooling operation
A
Stoppage function area
B
Indoor suction air temperature
C
Outdoor temperature
The limitation of the permissible outdoor temperature area in
cooling operation (factory-set) as shown in the right figure is
canceled.
0
25
17
15
19
26
27
30
A
B
C
(
o
C)
(
o
C)
(
o
C)
(
o
C)
6 Optional functions
132
SMGB0065 rev. 1 - 12/2010