Local Device Manager
104/166
Port X1...X8
Click on a
Port X1 ... X8
element in the
CONNECTED DEVICE
navigation tree to show details about the port configuration in the
Info
tab.
You can also change certain port configuration settings in the
Configuration
tab (for advanced users only).
Figure 87: Info tab of port
Port Info:
Parameter
Value/Description
Port Mode
Port mode according to setting in the
Configuration
tab.
Note
: Default mode for all ports is
IOL_AUTOSTART
. Other modes, except
DEACTIVATED
,
are not supported by the sensorEDGE.
Port Class
Always
Class A
.
Note
: Other classes are not supported by the sensorEDGE.
Pin2Support
Default is
true
.
Note
: Although by default set to
true
, digital inputs/outputs at pin 2 are not supported by the
sensorEDGE.
Pin2Configuration
Pin 2 configuration according to setting in the
Configuration
tab.
Note
: Although by default set to
Digital Input
, digital inputs/outputs at pin 2 are not
supported by the sensorEDGE.
Pin2ProcessData
Indicates whether a digital input signal is present at pin 2.
Note
: Digital inputs/outputs at pin 2 are not supported by the sensorEDGE. However, the
state
true
may occur if you have connected to this port an IO-Link sensor that also uses the
digital I/O channel B.
Pin4ProcessData
Indicates whether a digital input signal is present at pin 4.
Note
: Digital inputs/outputs at pin 4 (“channel A”) are not supported by the sensorEDGE.
Max Power Supply
Maximum power supply of port.
Parameter Identifier
Not used.
Actual Cycle Time
Actual cycle time of IO-Link communication. Default setting in the
Configuration
tab is
AFAP
(as fast as possible, i.e. depending on the capabilities of the sensor device).
netFIELD sensorEDGE | User manual
DOC200601UM01EN | Revision 1 | English | 2021-09 | Released | Public
© Hilscher 2021