7 Error Handling
Programmer PG 02
41
3050 ErrFeedback
3150 SerrFeedback
Cause:
Error in feedback system of actuator, actuator not connected.
Response:
- Governor cannot be put into operation.
- Emergency shutdown.
Actions:
- Check feedback cable to actuator.
- Check actuator, replace if necessary.
- Check error limits for feedback:
1952
FeedbackErrorLow
/ 1953
FeedbackErrorHigh
3051 ErrFeedback2
3151 SerrFeedback2
Cause:
Error in feedback system of actuator 2, actuator 2 not connected.
Response:
- Governor cannot be put into operation.
- Emergency shutdown.
Actions:
- Check feedback cable to actuator.
- Check actuator, replace if necessary.
- Check error limits for feedback:
1962
FeedbackErrorLow2
/ 1963
FeedbackErrorHigh2
Note:
These parameters are implemented only in the PRIAMOS III series.
3052 ErrFeedback3
3152 SerrFeedback3
Cause:
Error in feedback system of actuator 3, actuator 3 not connected.
Response:
- Governor cannot be put into operation.
- Emergency shutdown.
Actions:
- Check feedback cable to actuator.
- Check actuator, replace if necessary.
- Check error limits for feedback:
1972
FeedbackErrorLow
/ 1973
FeedbackErrorHigh
Note:
These parameters are implemented only in the PRIAMOS III series.