4 Starting the Engine
Programmer PG 02
17
- Preset
PID-values:
Number Parameter
Value
Unit
100
Gain
15 %
101
Stability
10 %
102
Derivative
0 %
- Parameterize the absolute limits of actuator travel:
Number Parameter
Value
Unit
310
ActPosSecureMin
3 %
312
ActPosSecureMax
97 %
- Adjust starting actuator position (type 1):
Number Parameter
Value
Unit
250
StartType
1
251
LimitsDelay
3 s
255
StartSpeed1
10 rpm
256
StartSpeed2
400 rpm
260
StartFuel1
60 %
-
Save values to the governor's memory and reset the governor.
5. Check speed pickup and determine starter speed.
- Operate the engine stop switch so that the engine cannot be started.
Indication:
Number Parameter
Value
Unit
2810
SwitchEngineStop
1
In case of a failure of the speed governor system or with a wrong
parametrizing the engine can go into overspeed!
Before the start of the engine therefore the function of the separate
overspeed protection must be guaranteed.
Danger