The red “No Connection” disappears and the values at the top
of the page start to change.
You are now connected from your PC to the HI 6600 weight
processor.
5)
On the Setup pull down menu select Poll Definition and
select the function 04 INPUT REGISTER and the
Adress 0 and Length as 8 +(8 * x) where x = the number of Weight Processing Modules to a maximum
of 120.
6)
On the Hardy Modbus-Link page. Display pull-down
menu, select Float Inverse.
The Weight value would be found in register 5 (net) or 6 (gross). Other registers are not float values so be
aware of random numbers in other registers. For example, the above would be 8 registers for the Cmd module
and 8 regular for each Weight Processing Module.