Chapter 5 - Calibration
5-7
N10:40 - 46
Location of data being written to M0 File.
N10:60 - 72
Locations of Parameters Values
N10:60
Units
N10:61
Number of Averages
N10:62
WAVERSAVER Setting
N10:63-64
0 Tolerance
N10:65-66
A0 Tolerance
N10:67-68
Motion
N10:69-70
CalLo
N10:71-72
Span
C2 Calibration
Ladder Logic
Explanation
This file will download and set a reference point for
C2 calibration and then save data to non-volatile
memory.
Rung #0
Does an initial read of the M1 file.
this is necessary to get the sequence
number for future writes.
Rungs #1-5
Downloads a reference point value.
These rungs follow the same pattern
as the SETPARAMS example in
Chapter 4.
Rungs #6-12
Writes the C2CALCMD to set the ref-
erence point. These rungs follow the
same pattern as setting a parameter in
the SETPARAMS example in Chapter
4.
Rungs #13-17 Writes the WRITENONVOLATILE
command. This will save the new cal-
ibration to the non-volatile memory.
These rungs follow the same pattern
as setting a parameter in the SET-
PARMS example in Chapter 4.
Summary of Contents for C Series
Page 8: ...HI 1746 WS WEIGHT SCALE MODULE vi...
Page 10: ...HI 1746 WS WEIGH SCALE MODULE II...
Page 46: ...HI 1746 WS WEIGH SCALE MODULE 4 16 I O Setup Ladder Logic for Remote Mode Operation...
Page 47: ...Chapter 4 Setup 4 17...
Page 54: ...HI 1746 WS WEIGH SCALE MODULE 4 24 SETPARAMS Remote Mode of Operation...
Page 55: ...Chapter 4 Setup 4 25...
Page 56: ...HI 1746 WS WEIGH SCALE MODULE 4 26...
Page 60: ...HI 1746 WS WEIGH SCALE MODULE 4 30...
Page 69: ...Chapter 5 Calibration 5 9...
Page 70: ...HI 1746 WS WEIGH SCALE MODULE 5 10 FIG 5 5 C2 LADDER LOGIC EXAMPLE LOCAL MODE OF OPERATION...
Page 74: ...HI 1746 WS WEIGH SCALE MODULE 5 14...
Page 84: ...HI 1746 WS WEIGH SCALE MODULE 6 10...
Page 92: ...HI 1756 WS MANUAL...