HI 1746-WS WEIGH SCALE MODULE
1-6
leveling and load sharing adjustments to the weighing
system. The Hardy Configuration Software is highly
recommended for use with this option.
Auto Zero
Auto Zero Tracking will indicate zero weight, as long
as any “live weight” on the scale is below the set Auto
Zero Tolerance and the scale is not motion. This capa-
bility allows the module to ignore material build-up in
the weighing system within a pre-set auto zero toler-
ance.
Note
The amount of weight zeroed off is cumulative. The
zero command will fail if the current gross weight plus
any previously zeroed amount exceeds the zero
tolerance.
Set Point TTL
Outputs
The HI 1746-WS is equipped with two (2) standard
Digital TTL (Transistor - Transistor Logic) Level
Outputs which can be connected to external solid state
relays. Both outputs have individual set point, preact
and deadband parameters. Both outputs are rated at 10
milliamps per line. Each can be programmed to
respond to the standard Net, Gross, Rate of Change
(ROC), Excitation Monitor, Force On or Force Off
mode of operation.
Summary of Contents for C Series
Page 8: ...HI 1746 WS WEIGHT SCALE MODULE vi...
Page 10: ...HI 1746 WS WEIGH SCALE MODULE II...
Page 46: ...HI 1746 WS WEIGH SCALE MODULE 4 16 I O Setup Ladder Logic for Remote Mode Operation...
Page 47: ...Chapter 4 Setup 4 17...
Page 54: ...HI 1746 WS WEIGH SCALE MODULE 4 24 SETPARAMS Remote Mode of Operation...
Page 55: ...Chapter 4 Setup 4 25...
Page 56: ...HI 1746 WS WEIGH SCALE MODULE 4 26...
Page 60: ...HI 1746 WS WEIGH SCALE MODULE 4 30...
Page 69: ...Chapter 5 Calibration 5 9...
Page 70: ...HI 1746 WS WEIGH SCALE MODULE 5 10 FIG 5 5 C2 LADDER LOGIC EXAMPLE LOCAL MODE OF OPERATION...
Page 74: ...HI 1746 WS WEIGH SCALE MODULE 5 14...
Page 84: ...HI 1746 WS WEIGH SCALE MODULE 6 10...
Page 92: ...HI 1756 WS MANUAL...