HI 1746-WS WEIGH SCALE MODULE
4-14
Error Return Values:
•
STATUSWORD - there was a conversion error,
weight in motion or an A/D error or all three.
•
C2FAILNODEVS - did not detect any C2 load
cells.
•
C2FAILCAPEQ - detected two load cells with
different capacities.
SEQ
NUMBER
0
COMMAND#
(Hex)
1
STATUS
2
OFFSET
3
LENGTH
4
DATA
5-16
From M1 File
0x66
Read C2 Serial
Number Command
(READC2SERIALN
UM)
The Read C2 Serial Number Command - Reads the 9
byte serial number from a C2 chip located on every
C2 load cell. Specify the index of the C2 chip to read
in commandData.offset of the Mfile. The index
should be a number of 0 to C2RomX-1 (-1 is a minus
one not a dash one), where C2RomX is the number of
C2 chips. The “serial number” will be 8 bytes of
ASCII text, followed by a 0 terminator.
Error Return Values:
•
OUTOFTOLERANCE - specified chip is not
found.
SEQ
NUMBER
0
COMMAND#
(Hex)
1
STATUS
2
OFFSET
3
LENGTH
4
DATA
5-16
From M1 File
0x70
Set Parameters
Command
(SETPARAM)
Sets a parameter in the module. (See Setting the Pro-
cess Weighing Parameters below for more detailed
information.)
Summary of Contents for C Series
Page 8: ...HI 1746 WS WEIGHT SCALE MODULE vi...
Page 10: ...HI 1746 WS WEIGH SCALE MODULE II...
Page 46: ...HI 1746 WS WEIGH SCALE MODULE 4 16 I O Setup Ladder Logic for Remote Mode Operation...
Page 47: ...Chapter 4 Setup 4 17...
Page 54: ...HI 1746 WS WEIGH SCALE MODULE 4 24 SETPARAMS Remote Mode of Operation...
Page 55: ...Chapter 4 Setup 4 25...
Page 56: ...HI 1746 WS WEIGH SCALE MODULE 4 26...
Page 60: ...HI 1746 WS WEIGH SCALE MODULE 4 30...
Page 69: ...Chapter 5 Calibration 5 9...
Page 70: ...HI 1746 WS WEIGH SCALE MODULE 5 10 FIG 5 5 C2 LADDER LOGIC EXAMPLE LOCAL MODE OF OPERATION...
Page 74: ...HI 1746 WS WEIGH SCALE MODULE 5 14...
Page 84: ...HI 1746 WS WEIGH SCALE MODULE 6 10...
Page 92: ...HI 1756 WS MANUAL...