HI 1746-WS WEIGH SCALE MODULE
1-4
measurement applications. By eliminating the factor
of vibratory forces the module is capable of identify-
ing the actual weight data. WAVERSAVER
®
can be
configured from the Configuration Software to ignore
noise with frequencies as low as 0.25 Hz. One of five
higher additional cut off frequencies may be selected
to provide a faster instrument response time. The
default factory configuration is 1.00 Hz vibration fre-
quency immunity.
C2
®
Calibration
C2 Second Generation Calibration enables a scale
system to be calibrated electronically without using
certified test weights which equals the systems load
capacity. A C2 weighing system consists of up to
eight (8) C2 load sensors, a junction box, interconnect
cable and an instrument with C2 capabilities such as
the HI 1746-WS Weight Scale Module. All Hardy C2
certified load sensors contain digital information
detailing its unique performance characteristics. The
HI 1746-WS reads the performance characteristics of
each individual load sensor and detects the quantity of
load sensors in the system. C2 Calibration can be per-
formed by pressing “The Button” located in the front
of the module, or via Hardy’s Configuration Software
or Allen-Bradley’s RS Logix 500 software.
IT
®
I
NTEGRATED
T
ECHNICIAN
™
is a system diagnostics
utility which continuously monitors the weighing sys-
tem (with up to 4 load sensors) for possible malfunc-
tions. For full functionality the HI 215IT junction box
and Hardy’s Configuration Software for Windows
should be used. Full
IT
functionality allows the opera-
tor to rapidly troubleshoot a weighing system from
the Configuration Software, I
NTEGRATED
T
ECHNI-
CIAN
Display.
Excitation Monitor
Continuously monitors a system’s excitation current
to check for open or shorted load sensors or damaged
or broken excitation wire(s), including the wires
between the module and the
IT
Junction box. If the
measured current deviates more than a +/- 10% toler-
ance, an “Excitation Error” bit (Module Status Word
bit 9) is set to 1.
Summary of Contents for C Series
Page 8: ...HI 1746 WS WEIGHT SCALE MODULE vi...
Page 10: ...HI 1746 WS WEIGH SCALE MODULE II...
Page 46: ...HI 1746 WS WEIGH SCALE MODULE 4 16 I O Setup Ladder Logic for Remote Mode Operation...
Page 47: ...Chapter 4 Setup 4 17...
Page 54: ...HI 1746 WS WEIGH SCALE MODULE 4 24 SETPARAMS Remote Mode of Operation...
Page 55: ...Chapter 4 Setup 4 25...
Page 56: ...HI 1746 WS WEIGH SCALE MODULE 4 26...
Page 60: ...HI 1746 WS WEIGH SCALE MODULE 4 30...
Page 69: ...Chapter 5 Calibration 5 9...
Page 70: ...HI 1746 WS WEIGH SCALE MODULE 5 10 FIG 5 5 C2 LADDER LOGIC EXAMPLE LOCAL MODE OF OPERATION...
Page 74: ...HI 1746 WS WEIGH SCALE MODULE 5 14...
Page 84: ...HI 1746 WS WEIGH SCALE MODULE 6 10...
Page 92: ...HI 1756 WS MANUAL...