Chapter 4 - Setup
4-13
Cal Low Command
(CALLOWCMD)
The Cal Low Command - sets the “calLowCount”
parameter to the current A/D average counts when
doing a hard calibration.
Error Return Values:
•
STATUSWORD - there was a conversion error,
weight in motion or an A/D error or all three.
•
HARDCALFAILCOUNTS - there is less than
100 counts between the zero and the span
weights.
SEQ
NUMBER
0
COMMAND#
(Hex)
1
STATUS
2
OFFSET
3
LENGTH
4
DATA
5-16
From M1 File
0x64
Cal High
Command
(CALHIGHCMD)
The Cal High Command - Sets the Span Weight
parameter to the current A/D average counts when
doing Hard CAL.
Error Return Values:
•
STATUSWORD - there was a conversion error,
weight in motion or an A/D error or all three.
•
HARDCALFAILCOUNTS - there is less than
100 counts between the zero and the span
weights.
SEQ
NUMBER
0
COMMAND#
(Hex)
1
STATUS
2
OFFSET
3
LENGTH
4
DATA
5-16
From M1 File
0x65
C2 Cal Command
(C2CALCMD)
The C2 Cal Command - Performs a C2 Calibration.
Summary of Contents for C Series
Page 8: ...HI 1746 WS WEIGHT SCALE MODULE vi...
Page 10: ...HI 1746 WS WEIGH SCALE MODULE II...
Page 46: ...HI 1746 WS WEIGH SCALE MODULE 4 16 I O Setup Ladder Logic for Remote Mode Operation...
Page 47: ...Chapter 4 Setup 4 17...
Page 54: ...HI 1746 WS WEIGH SCALE MODULE 4 24 SETPARAMS Remote Mode of Operation...
Page 55: ...Chapter 4 Setup 4 25...
Page 56: ...HI 1746 WS WEIGH SCALE MODULE 4 26...
Page 60: ...HI 1746 WS WEIGH SCALE MODULE 4 30...
Page 69: ...Chapter 5 Calibration 5 9...
Page 70: ...HI 1746 WS WEIGH SCALE MODULE 5 10 FIG 5 5 C2 LADDER LOGIC EXAMPLE LOCAL MODE OF OPERATION...
Page 74: ...HI 1746 WS WEIGH SCALE MODULE 5 14...
Page 84: ...HI 1746 WS WEIGH SCALE MODULE 6 10...
Page 92: ...HI 1756 WS MANUAL...