HI 1746-WS WEIGH SCALE MODULE
5-2
Contents) is vertically passed through a
load cell. (See Fig. 5-1)
b.
Check to see that nothing is binding the
load cell. This means that nothing is
draped across the scale/vessel or the
load cell, such as a hose, electrical cord,
tubes, or other objects.
c.
Check to see that nothing is coming in
contact with the scale/vessel other than
service wires and piping that have been
properly mounted with flexible connec-
tors.
FIG. 5-1 PROPERLY INSTALLED LOAD CELL W/NO BINDING
Electrical Check
Procedures
Load Cell/Point
Input/Output
Measurements
Step 3.
Typical Load Cell/Point Input/Output
Measurements (EXC & SIG Outputs)
a.
The HI 1746-WS is designed to supply 5
VDC excitation to as many as eight 350
Ohm load cells/points.