78
Vol. 2.6 © 2020 Hanbell Precise Machinery Co., Ltd. All rights reserved
Table 5.2 MCC&LRA of low voltage models
Note
:
Cooler standard equipment Motor A, able to operate the maximum load condition is about CT / ET
= 40/13
℃
, the heating machine operating condition is about CT / ET = 52/14
℃
, a slightly different
from the actual horsepower during the motor design. The actual maximum continuous operation
current (MCC) should be in accordance with the above table. When the actual operating conditions
of the unit exceeds the MCC value, please use Motor B and state for Motor B on the purchasing
order instead.
Caution
:
1. This table stated rated current and LRA for Motor design performance are not referring to the
compressor operating rated current.
Caution
:
2. The value of MCC in this table is related to the maximum temperature rise (90 °C) of the Motor
and is irrelevant to motor power (size). Therefore, a voltage drop in the power supply will cause
motor temperature rise (refer to Motor Coil Temperature Sensor Pt100 or Pt100 Description).
5.3.5 Grounding
Grounding point in electric system normally is a neutral point. Exposed compressor
conductor should not be electrified in normal use. But there is possibility that the
compressor is electrified under malfunction condition. For security purpose, HANBELL
strongly recommends to ensure the grounding during installation.
Suggestion:
a. Dedicated M12 grounding screw (instructed in terminal box) should be reliably
connected with grounding wire.
Motor
Power
( kW)
Voltage
(V)
Rated
current(A)
MCC
(A)
LRA
(A)
Motor
Power
( kW)
Voltage
(V)
Rated
current(A)
MCC
(A)
LRA
(A)
6kV
73
88
440
3.3kV
136
163
917
10kV
44
53
253
4.16kV
106
127
675
6.6kV
67
81
445
11kV
40
48
230
6kV
92
110
668
3.3kV
168
202
1,235
10kV
54
65
342
4.16kV
132
158
952
6.6kV
83
99
591
11kV
49
59
314
6kV
80
97
473
3.3kV
146
175
924
10kV
48
58
296
4.16kV
116
139
764
6.6kV
73
87
470
11kV
43
52
273
6kV
100
121
681
3.3kV
182
218
1,269
10kV
60
72
369
4.16kV
145
174
1,016
6.6kV
91
109
629
11kV
54
65
338
6kV
80
97
473
3.3kV
146
175
924
10kV
48
58
296
4.16kV
116
139
764
6.6kV
73
87
470
11kV
43
52
273
6kV
92
110
668
3.3kV
168
202
1,235
10kV
54
65
342
4.16kV
132
158
952
6.6kV
83
99
591
11kV
49
59
314
6kV
107
129
748
3.3kV
194
233
1,348
10kV
63
76
407
4.16kV
154
184
1,096
6.6kV
97
116
692
11kV
57
69
373
6kV
123
147
802
3.3kV
222
267
1,547
10kV
74
89
502
4.16kV
176
212
1,178
6.6kV
111
133
743
11kV
66
79
456
RT-240(E)
A
960
1,100
60Hz
RT-301
660
A
960
A
B
1,100
B
RT-221
A
720
A
720
B
820
B
820
820
RT-260(E)
RT-280(E)
A
720
A
720
B
900
B
900
B
A
660
B
820
Modle
50Hz