Chapter 5. Motor
5.1 Motor cooling
The motor in RT series compressor is cooled by liquid refrigerant that comes from the
condenser. Solenoid valves, expansion valves, or orifices should be installed on piping
before the suction flange as a throttle for inflow control. In order to keep the motor
temperature between30~90
℃
, it is estimated that heat exchange is equal to around 6~10%
of motor power input for motor cooling.
Figure 5.1Motor cooling system
Figure 5.2 Two aux inlets for cooling
Note1: Two auxiliary injection inlets on the motor casing are the main source of motor coil
cooling; please make sure both of them are connected.
Note2
:
Change of the two auxiliary liquid injection connectors is prohibited.
2 aux injection
inlets
Main injection
inlet
Aux injection
outlet
Main injection outlet