125
2.3 Outdoor unit control
2.3.1 Outdoor frequency control
A. Compressor running frequency range: 1U: 30-91RPS 3U19:20-100RPS 3U24:20-94RPS, the others are
20~95RPS
B. defination of high-efficiency operation and its frequency control
In order to meet the cooling request at a high ambient temperature and the heating request at low ambient
temperature, we set the high-efficiency operation.
Entering condition: cooling mode, Tao≥33
o
C( E), heating mode, Tao≤5
o
C( E)
2.3.2 Electronic expansion valve (EEV) control
A: Electronic characteristic
Max. open angle
500 pulse
Driving speed
PPS
B: Initialization of EEV
EEV driving speed: open direction: 32MS; close direction: 32MS
C: Open angle limitation of EEV
Unitary
Unit stop
Adjustable upper limit
Cool/dry
250(E)
480(E)
heat
250(E)
480(E)
Unit stop
Adjustable upper
limit
Thermostat ON
Thermostat OFF Adjustable lower
limitation
Cool/ dry 5(E)
450(E)
Standard open
angle+tolerance 5(E)
80(E)
Heat
60(E)
450(E)
Standard open
angle+tolerance 60(E)
80(E)
D: Standard open angle control
Unitary: In Cool/Dry mode, standard open angle: outdoor ambient temp.≥22
o
C, 260pulse (E);Outdoor ambient
temp.≤22
o
C, 210pulse (E);
In heat mode, standard open angle: outdoor ambient temp.≥6
o
C, 240pulses (E) ;Outdoor ambient
temp. ≤6
o
C, 160pulse (E)
Multi: In Cool/Dry mode, standard open angle: outdoor ambient temp.≥20
o
C, 250 pulse(E);Outdoor ambient
temp.<20
o
C, 210 pulse(E);
In Heat mode, standard open angle: outdoor ambient temp.≥10
o
C, pulse (E);outdoor ambient
temp.<10
o
C, 210 pulse (E).
F: When discharging temp. Td is too high or too low, modify the EEV angle Unitary
Mode
Modification process
Max. modification
Cooling
If TD>106 degree and -1 degree /2 minutes, open angle keeps between 106-50. -3
Cooling
If TD<50 degree and +1 degree /2 minutes, open angle keeps between 50-106. +3
Heating
If TD>100 degree and -1 degree /2 minutes, open angle keeps between 100-50. -3
Heating
If TD<50 degree and +1 degree /2 minutes, open angle keeps between 50-100. +3
Multi: In order to cooperate the compressor discharging temp. over high protection, the system will enlarge the
EEV open angle. Within 5 minutes after compressor starts up, it will not modify. The detecting period is 30 seconds.
Summary of Contents for AB25S2SC1FA
Page 1: ...SYJS 04 2017 REV A Edition 2017 04 service manual R32...
Page 3: ...1 Part 1 General Information 1 Indoor outdoor unit models 2 2 Feature 3...
Page 23: ...21 5 Installation For AB25S2SC1FA AB35S2SC1FA 1 Installation procedure...
Page 24: ...22 AB25S2SC1FA AB35S2SC1FA AB25S2SC1FA AB35S2SC1FA...
Page 25: ...23...
Page 26: ...24...
Page 27: ...25 AB25S2SC1FA AB35S2SC1FA...
Page 28: ...26...
Page 29: ...27 For AD25S2SC1FA AD35S2SC1FA Installation procedure AD25S2SS1FA AD35S2SS1FA...
Page 30: ...28 AD25S2SS1FA AD35S2SS1FA AD25S2SS1FA AD35S2SS1FA...
Page 31: ...29...
Page 32: ...30 AD25S2SS1FA AD35S2SS1FA...
Page 33: ...31...
Page 38: ...36 21mm AD50S2SM1FA AD71S2SM1FA Unit model The size of drain opening...
Page 39: ...37...
Page 54: ...52 2 Dimension 1U71S2SM1FA 860 633 unit mm...
Page 91: ...89 R32 R32 R32 R32 R32 R32 R32 R32 R32 10 2 Read before installation...
Page 92: ...90 3 R32 R32 R32 R32 R32 R32 R32...
Page 93: ...91 R32 R32 R32 R32 R32 R32 R32 R32 10A HFC 410A...
Page 96: ...94 10 5 Air tightness test...
Page 97: ...95 R32 R32 10 6 Vacuuming...
Page 123: ...121 PCB 0011800410RA 1U71S2SG1FA Power module 0011800377C 1U71S2SG1FA...