118
1.3.12 Compulsory defrosting operation
A: After indoor receives the compulsory defrosting signal, it will send continously the signal to outdoor for 10
times, in this period, indoor unit will work normally and it will enter defrosting operation until it receives the enter-
defrost signal from outdoor unit.
B: Wired control type: In heating mode, make a jumper for D2 to enter compulsory defrosting.
C: Remote control type: In heating mode, high speed, 30
o
C, press SLEEP button 6 times, and the buzzer will
sound 3 times, then enter the manual defrosting.
1.3.13 Trial operation
A: Enter condition
a: Wired control type: In OFF state of COOL or HEAT mode, press ON/OFF button for over 5 seconds to enter
the cooling or heating trial operation;
b: Remote control type: In OFF state, keep pressing ON/OFF button until 5 seconds later, the buzzer sounds
twice, then enter the cooling or heating trial operation;
B: Response in trial operation
a: Cooling trial operation: indoor sends S-CODE=SD to outdoor, indoor: at high speed, set temp: 16
o
C;
b: Heating trial operation: indoor sends S-CODE=SF to outdoor, indoor: at high speed, set temp: 30
o
C;
c: In this period, anti-freezed and overheat functions are invalid.
C: Quit condition
a: Receiving the signal of cancelling trial operation from wired controller or remote controller;
b: After trial operation has run for 20 minutes, it will quit trial operation automatically and enter the normal mode
with the set temp.: 24
o
C.
1.3.14 Timer operation
A: Wired control type: wired controller will control the unit ON/OFF;
B: Remote control type: indoor unit will confirm the unit ON or OFF according to the current clock and the timer
clock set by remote controller. When setting timer function, the timer LED will be ON.
1.3.15 SLEEP function
A: Wired control type unit is without sleep function;
B: Remote control type unit consists of cooling sleep and heating sleep, after the sleep is set, the unit will
change mode; the sleep will begin to count.
a: In cooling/dry mode, after running for 1 hour, the set temp. will increase 1
o
C, another 1 hour later, the
set temp. will increase 1
o
C again, then 6 hours (or set time-2) later , it will stop.
b: In heating mode, after running for 1 hour, the set temp. will reduce 2
o
C, another 1 hour later, the set temp. will
reduce 2
o
C again, then 3 hours later, the set temp. will increase 1
o
C, and another 3 hours(or set time-5), it will
stop.
c: When setting sleep function, indoor motor is forced at low speed.
1.3.16
Healthy negative ion function
When receiving the healthy signal from the wired controller or remote controller, if fan motor is running, the
negative ion will work;
If the fan motor stops, the negative ion generator will stop.
1.3.17
Auto-restart function
A: Wired control type:
YR-E17:
Please refer to the DIP switch setting SW4: ON means auto-restart unavailable; OFF means auto-
restart available(SW4=OFF is factory default setting)
B: Remote control type:
YR-HBS01:
In 5 seconds, press SLEEP button 10 times continuously, the buzzer will beep 4 times and enter auto-restart
Summary of Contents for AB25S2SC1FA
Page 1: ...SYJS 04 2017 REV A Edition 2017 04 service manual R32...
Page 3: ...1 Part 1 General Information 1 Indoor outdoor unit models 2 2 Feature 3...
Page 23: ...21 5 Installation For AB25S2SC1FA AB35S2SC1FA 1 Installation procedure...
Page 24: ...22 AB25S2SC1FA AB35S2SC1FA AB25S2SC1FA AB35S2SC1FA...
Page 25: ...23...
Page 26: ...24...
Page 27: ...25 AB25S2SC1FA AB35S2SC1FA...
Page 28: ...26...
Page 29: ...27 For AD25S2SC1FA AD35S2SC1FA Installation procedure AD25S2SS1FA AD35S2SS1FA...
Page 30: ...28 AD25S2SS1FA AD35S2SS1FA AD25S2SS1FA AD35S2SS1FA...
Page 31: ...29...
Page 32: ...30 AD25S2SS1FA AD35S2SS1FA...
Page 33: ...31...
Page 38: ...36 21mm AD50S2SM1FA AD71S2SM1FA Unit model The size of drain opening...
Page 39: ...37...
Page 54: ...52 2 Dimension 1U71S2SM1FA 860 633 unit mm...
Page 91: ...89 R32 R32 R32 R32 R32 R32 R32 R32 R32 10 2 Read before installation...
Page 92: ...90 3 R32 R32 R32 R32 R32 R32 R32...
Page 93: ...91 R32 R32 R32 R32 R32 R32 R32 R32 10A HFC 410A...
Page 96: ...94 10 5 Air tightness test...
Page 97: ...95 R32 R32 10 6 Vacuuming...
Page 123: ...121 PCB 0011800410RA 1U71S2SG1FA Power module 0011800377C 1U71S2SG1FA...