127
the defrosting temp. sensor Te and outdoor ambient temp. sensor Tao, if they can meet the following condition,
entering in defrosting operation.
1. 5
o
C<(E)<Tao,Te<=-6
o
C<(E);
2. -6
o
C<(E)<=Tao<=5
o
C,Te≤C×Tao-α;
Herein :α=8(E) ;C:Tao<0
o
C;C=0.8; Tao≥0
o
C,C=0.6;
3.Tao<-6
o
C,Te≤-15
o
C<(E)and defrosting compressor run for 48 minutes in all.
Multi:
a. In heating mode, if the compressor has run for 10 minutes continously and run for 45 minutes in all, the
system will measure the defrosting temperature sensor Te and outdoor ambient temp. sensor TA, if the below
condition can be met for continous 5 minutes, the unit will enter defrosting operation:
Te≤C×TA-α
Herein: C: TA<0
o,
C=0.8 TA≥0
o
C, C=0.6
According to SW5-2, the setting is as follow: in the place easy to frost, it is H; when out of factory, it is M.
Jumper selection M (out of factory) H
α (
o
C)
8 (E)
6 (E)
b. Defrosting entering condition: -15
o
C≤C×TA-α≤-2
o
C;
c. Stop and Pause condition of compressor running accumulative time in heating mode:
Checking Stop: running operation changes from heating to cooling.
Checking Pause: thermostat OFF, or the unit stops.
Cancel condition:
It will take the max. 10 minutes from beginning defrosting to quit it. Te sensor will measure the condition of
outdoor heat exchanger, if the temp. is over 7
o
C for 60 seconds in all or is up to 12
o
C for 30 seconds in all, the
defrosting will be over.
2.3.6 Compulsory defrosting control
Enter condition: in heating mode, after receiving the compulsory defrosting signal from indoor unit, the unit will
perform the compulsory defrosting operation.
Cancel condition: Te≥12
o
C and keep for 1 minute or the defrosting time is over 10 minutes. The manual
defrosting signal of indoor unit will remain until the outdoor enters defrosting mode.
Note: When outdoor compressor not running, the unti still can enter manual defrosting, but it will comply with the
3-minute protection of compressor.
Summary of Contents for AB25S2SC1FA
Page 1: ...SYJS 04 2017 REV A Edition 2017 04 service manual R32...
Page 3: ...1 Part 1 General Information 1 Indoor outdoor unit models 2 2 Feature 3...
Page 23: ...21 5 Installation For AB25S2SC1FA AB35S2SC1FA 1 Installation procedure...
Page 24: ...22 AB25S2SC1FA AB35S2SC1FA AB25S2SC1FA AB35S2SC1FA...
Page 25: ...23...
Page 26: ...24...
Page 27: ...25 AB25S2SC1FA AB35S2SC1FA...
Page 28: ...26...
Page 29: ...27 For AD25S2SC1FA AD35S2SC1FA Installation procedure AD25S2SS1FA AD35S2SS1FA...
Page 30: ...28 AD25S2SS1FA AD35S2SS1FA AD25S2SS1FA AD35S2SS1FA...
Page 31: ...29...
Page 32: ...30 AD25S2SS1FA AD35S2SS1FA...
Page 33: ...31...
Page 38: ...36 21mm AD50S2SM1FA AD71S2SM1FA Unit model The size of drain opening...
Page 39: ...37...
Page 54: ...52 2 Dimension 1U71S2SM1FA 860 633 unit mm...
Page 91: ...89 R32 R32 R32 R32 R32 R32 R32 R32 R32 10 2 Read before installation...
Page 92: ...90 3 R32 R32 R32 R32 R32 R32 R32...
Page 93: ...91 R32 R32 R32 R32 R32 R32 R32 R32 10A HFC 410A...
Page 96: ...94 10 5 Air tightness test...
Page 97: ...95 R32 R32 10 6 Vacuuming...
Page 123: ...121 PCB 0011800410RA 1U71S2SG1FA Power module 0011800377C 1U71S2SG1FA...