111
•
Test running.
1) To test cooling, set the lowest temperature at 16 °C. To test heating, set the highest temperature, at 30 °C. If the
temperature is lower than
16 °C, it is impossible to test cooling with remote controller, and also when the temperature is higher than 30 °C, it
is impossible to test heating.
2) Please check both cooling and heating operation of each unit individually and then also check the simultaneous
operation of all indoor units.
3) After running the unit for about 20 minutes, check the indoor unit outlet temperature.
4) After the unit is stopped, or working mode changed, the system will not start again for about 3 minutes.
5) During cooling operation, frost may occur on the indoor unit or pipes, this is normal.
•
Communication LED
3U52S2SG1FA and 3U68S2SG1FA are with 3 green LED that means 3 indoor units, 4U70S2SH1FA and
4U85S2SH1FA with 4 green LED
means 4 indoor units. If one LED keep lighting that means the corresponding indoor unit has good communication
with outdoor unit. If one LED is not lighting, that means there is no communication between indoor and outdoor.
Notes:
1) When using this product, you need not to set the address. But the L/N wires between indoor & outdoor units
must be corresponded, or there will be communication failure.
2) Quiet Operation Setting. Set the DIP "8" to ON position of SW5, the system will run with lower noise, but the
max. capacity will also reduce slightly.
3) Do not change the settings of other switchs, wrong settings can make the system damage or other malfunctions.
6) Operate the unit according to the operation manual. Please kindly explain to our customers
how to operate through the instruction manual.
•
Seven-segment numeric display
1) When unit is running, this seven-segment numeric will display the frequency of compressor.
For example, "
" means compressor running frequency is 40 Hz, "
" means compressor
running frequency is 108Hz.
2) When faulty happens, seven-segment numeric will flash and display some numbers, this
number is failure code. For example, a flashing "
" means No.15 failure, that is indoor and
outdoor communication error.
Summary of Contents for AB25S2SC1FA
Page 1: ...SYJS 04 2017 REV A Edition 2017 04 service manual R32...
Page 3: ...1 Part 1 General Information 1 Indoor outdoor unit models 2 2 Feature 3...
Page 23: ...21 5 Installation For AB25S2SC1FA AB35S2SC1FA 1 Installation procedure...
Page 24: ...22 AB25S2SC1FA AB35S2SC1FA AB25S2SC1FA AB35S2SC1FA...
Page 25: ...23...
Page 26: ...24...
Page 27: ...25 AB25S2SC1FA AB35S2SC1FA...
Page 28: ...26...
Page 29: ...27 For AD25S2SC1FA AD35S2SC1FA Installation procedure AD25S2SS1FA AD35S2SS1FA...
Page 30: ...28 AD25S2SS1FA AD35S2SS1FA AD25S2SS1FA AD35S2SS1FA...
Page 31: ...29...
Page 32: ...30 AD25S2SS1FA AD35S2SS1FA...
Page 33: ...31...
Page 38: ...36 21mm AD50S2SM1FA AD71S2SM1FA Unit model The size of drain opening...
Page 39: ...37...
Page 54: ...52 2 Dimension 1U71S2SM1FA 860 633 unit mm...
Page 91: ...89 R32 R32 R32 R32 R32 R32 R32 R32 R32 10 2 Read before installation...
Page 92: ...90 3 R32 R32 R32 R32 R32 R32 R32...
Page 93: ...91 R32 R32 R32 R32 R32 R32 R32 R32 10A HFC 410A...
Page 96: ...94 10 5 Air tightness test...
Page 97: ...95 R32 R32 10 6 Vacuuming...
Page 123: ...121 PCB 0011800410RA 1U71S2SG1FA Power module 0011800377C 1U71S2SG1FA...