For AD50S2SM1FA/AD71S2SM1FA
Installation procedure
1. Applicable ambient temperature range:
The machine is adaptive in following situation
Cooling
Heating
Indoor temperature
Outdoor temperature
Indoor temperature
Outdoor temperature
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
32/23 C
18/14 C
46/26 C
10/6 C
27 C
15 C
24/18 C
-15 C
2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person.
3. If the fuse on the indoor PC board is broken please change it with the type of T 6.3A /250VAC(For series 24,28,36,48).
4. The wiring method should be in line with the local wiring standard.
5. The power cable should be:
H05RN-F 3G 4.0mm
2
;
The connecting cable should be:
H05RN-F 4G 2.0mm
2
All the cables shall have got the European authentication certificate. During installation, when the connecting cables
break off, it must be assured that the grouding wire is the last one to be broken off.
6. The power cable and connect cable should be self-provided.
7. The breaker of the air conditioner should be all-pole switch, and the distance between its two contacts should be no
less than 3mm.
8. The indoor unit installation height is at least 2.5m.
9. A leakage breaker must be installed.
10.For
AD50S2SM1FA AD71S2SM1FA,we
can get the 10 different ESP through adjust wired controllerYR-E17,please refer
below:
AD50S2SM1FA AD71S2SM1FA
St
actic
pressure
grade
1
2
3
5
4
7
6
8
9
10
St
acti
c pressure 25Pa
37Pa
50Pa
70Pa
90Pa
100Pa
110Pa
120Pa
130Pa
150Pa
Adjsutment metchod bywired controller YR-E17
:
In the state of ON and non screen saving state, press Fan+ Set keys for
5s to enter sta
ti
c pressure grade adjustmentstate with sta
ti
c pressure icon
flashing
and current sta
ti
cpressure grade
sta
ti
cally displaying. Press key
↑↓
to changesta
ti
c pressure grade, then press Set key to con
fi
rm.
Details please refer to wired controller opera
ti
on & installa
tion
manual.
Adjsutment metchod by Infrared remote conInfrared receiver RE-02
:
Step a:
set the Infrared remote controller at
co
ndition
:
FAN mode
,
fan speed high
Step b
:then aim the remote controller at the infrared remote receiver RE-02
,
press HEALTH bu
tt
on 4+N
ti
mes
(
1
≤
N
≤
10
,
integer
)
within 12 seconds
,
then the receiver will beep N+1
times
,
the
sta
ti
c pressure level N is been set successfully.
Note
:
For Infrared remote controller YR-HBS01, need press ON/OFF bu
tt
on make the controller’s at OFF status
fi
rst
,
then
open the bu
tt
on cover press FRESH bu
tt
on will enter FAN mode interface.
Summary of Contents for AB25S2SC1FA
Page 1: ...SYJS 04 2017 REV A Edition 2017 04 service manual R32...
Page 3: ...1 Part 1 General Information 1 Indoor outdoor unit models 2 2 Feature 3...
Page 23: ...21 5 Installation For AB25S2SC1FA AB35S2SC1FA 1 Installation procedure...
Page 24: ...22 AB25S2SC1FA AB35S2SC1FA AB25S2SC1FA AB35S2SC1FA...
Page 25: ...23...
Page 26: ...24...
Page 27: ...25 AB25S2SC1FA AB35S2SC1FA...
Page 28: ...26...
Page 29: ...27 For AD25S2SC1FA AD35S2SC1FA Installation procedure AD25S2SS1FA AD35S2SS1FA...
Page 30: ...28 AD25S2SS1FA AD35S2SS1FA AD25S2SS1FA AD35S2SS1FA...
Page 31: ...29...
Page 32: ...30 AD25S2SS1FA AD35S2SS1FA...
Page 33: ...31...
Page 38: ...36 21mm AD50S2SM1FA AD71S2SM1FA Unit model The size of drain opening...
Page 39: ...37...
Page 54: ...52 2 Dimension 1U71S2SM1FA 860 633 unit mm...
Page 91: ...89 R32 R32 R32 R32 R32 R32 R32 R32 R32 10 2 Read before installation...
Page 92: ...90 3 R32 R32 R32 R32 R32 R32 R32...
Page 93: ...91 R32 R32 R32 R32 R32 R32 R32 R32 10A HFC 410A...
Page 96: ...94 10 5 Air tightness test...
Page 97: ...95 R32 R32 10 6 Vacuuming...
Page 123: ...121 PCB 0011800410RA 1U71S2SG1FA Power module 0011800377C 1U71S2SG1FA...