16
13
EC 051
kWh
Input 1
Input 2
0,6 A
24 V
I
1
I
2
F1
R = 1kΩ*
Technical changes reserved
Application example
Input 1: I1 state contact (ACB, MCCB position…)
Input 2: pulse contact from EC051.
The energy server is able to read output pulses of any Hager products,
or any manufacturer compliant with the IEC 62053-31E1,
class A standard.
Single phase counter direct 32A products EC051.
Single phase counter direct 63A products EC150, EC152 and EC154M.
Three phases counter direct 63A products EC350 and EC352.
Three phases counter direct 100A products EC360, EC362, EC364M
and EC365B.
Three phases counter via current transformer product EC370
and EC372.
*Note: if you connect a EC051, you must wire a 1kΩ resistor
(not supplied) in series. (Resistor not necessary for the EC15x, EC3xx)
HTG410H
Power supply and Input / Output cabling