19
Technical changes reserved
HTG410H
Power supply and Input / Output cabling
6.5 Pt100 temperature device
The energy server allows the internal cabinet or room temperature
measure through a resistance temperature device PT100.
Reference HTG445H (cable 3 meters)
Length and cross section
Up to 3 m max,
0,25 mm² minimum
Type of cable
Screened twisted pair cable
Reading frequency
1 Hz
Amplitude
-35°C to 100°C
Accuracy
± 0.7°C
Tolerance class
B
Applicable standard
EN 60751
QC small
(mm
2
)
0.2…1.5
(mm
2
)
0.2…1.5
/
(mm)
8
(mm
2
)
Connections
Output
Analog
Input 1 Input 2
0-10 V
4-20 mA
Input
PT100