23
Technical changes reserved
HTG410H
Devices installation and settings
7.1.1.4.2 Setting the transfer rate
Press button
to access this configuration item.
Example: COM bdS = 4,8
7.1.1.5 To quit and save programming
7.1.1.4.3 Setting the parity
Press button
to access this configuration item.
Example: COM PAr = Odd
When the communication is established between the master and the
slave, the activity indicator "COM" is blinking on the display.
7.1.1.6 Function test for the electrical wiring connections
During testing, device SM101C must be supplied with current and
voltage to all connections. Testing requires a power factor of the ins-
tallation between 0.6 and 1. If the power factor of the installation falls
outside this range, the test cannot be performed. In the case of 4 BL
/ 3 BL / 2 BL / 1 BL only the connection of the current transformer is
tested. In the case of 4 NBL and 3 NBL the connection as a whole is
controlled.
7.1.1.4.4 Setting the stop bit
Press button
to access this configuration item.
Example: COM StOP = 2
Error
Error description
Err0
There is no error
Err 1 / 2 / 3
Reversed polarity of current transformer on phase 1 /
phase 2 / phase 3
Err4
Reversed polarity of voltage between V1 and V2
Err5
Reversed polarity of voltage between V2 and V3
Err6
Reversed polarity of voltage between V3 and V1
Prog 3 sec.
1x
1x
1x
confirm
confirm
confirm
1x
1x
1x
1x (Odd)
2x (Even)
3x (nO)
1x (1)
2x (2)
1x (2,4)
2x (4,8)
3x (9,6)
4x (19,2)
5x (38,4)