Technical changes reserved
7.7.2 Programming mode
HTG410H
Automatic Transfer Switch HIC4xxE
Programming access is possible in automatic or manual mode,
when the product is in a stable position (I, 0 or II) with at least one
supply source available.
Programming is not accessible whilst any cycle sequence is running.
Navigation in the programming menu
- To enter the programming menu press and hold the validation key until "SETUP" appears on the screen
or
- For parameter access: Press the "up - down" or "left - right" keys to navigate.
Exiting programming mode without saving
- To quit programming mode without saving briefly press the "ESC" key. This will allow navigating back
to the main menu.
Note: Whilst in programming mode, should the product remain idle for longer than 2 minutes it will
automatically exit and return to the main menu without saving.
Programming
- Navigate to the parameter to be changed and press the validation key.
Note: The product will request a password
+
+
- Input the password by using the "up - down" keys to change the value and the "left - right" keys to
change the curser position. (The default factory setting is 1000).
- Press the validation key to validate the password and enable programming.
+
+
- Change the parameter value by using the "up - down" keys to change the variable and the "left - right"
keys to change the curser position.
- Press the validation key to validate the change
- if necessary, navigate to other parameters in the menu, change the value and validate each change.
- To save all changes, press and hold the validation key until "SAVED" is displayed.
Note: After saving, "SAVED" will be displayed for 2s, the product will automatically exit programming mode