61
LED
PROG
MOVE ON
TO THE NEXT MENU
PROG
x1 (STOP 2)
x2 (STOP 1)
PROG
x1 (STOP 2)
x2 (STOP 1)
Technical changes reserved
HTG410H
Modbus energy meters
7.2.5.9 Setting the communication stop bit
7.2.5.10 Quit and save programming
Scroll with button B to select stop bit 1 or 2
Example: STOP = 2
Press button C "Prog" for at least 5 seconds
x1 (5s)
Warning
The programming level is exited automatically after two
minutes if no input is made. Changes will not be saved!
7.2.5.11 Function test for the electrical wiring connections
The energy meter must be connected to the voltage supply and a
load must be connected. This function can only be used if the power
factor of the installation is between 0.6 and 1 and minimum current
consumed on each phase = 20 % In.
Press and hold button B for at least 3 seconds.
The messages below indicate you the connection status of phases in
the meter device.
Press button B for at least 3 seconds to exit this mode.
x1 (3s)
Error
Error description
Err 0
no error
Err 1 / 2 / 3
Reverse polarity of current transformer on phase 1/phase2/phase3
Err 4
Reversed polarity of voltage between V1 and V2
Err 5
Reversed polarity of voltage between V2 and V3
Err 6
Reversed polarity of voltage between V3 and V1
Err 7
reversed connection of voltage between V1 and neutral conductor
Err 8
reversed connection of voltage between V2 and neutral conductor
Err 9
reversed connection of voltage between V3 and neutral conductor