Function of the Energy trip unit
3.4 Managing alarms and logs
Measurement monitored
Possible
activation
conditions
Activation/
deactivation
threshold ranges
Version
3P
Version
4P
Average currents over interval
(Demand currents)
I1_dmd, I2_dmd, I3_dmd,
Iavg_dmd
>
<
0.2xIn to 10xIn
(increments of 0.1 A)
X
X
Current request IN_dmd
>
<
0.2xIn to 10xIn
(increments of 0.1 A)
–
X
Averaged power over interval (Demand power)
Total active power Pdmd
>
<
1 kW to 3000 kW
(increments of 0.1 kW)
X
X
Total reactive power Qdmd
>
<
1 kvar to 3000 kvar
(increments of 0.1
kvar)
X
X
Total apparent power Sdmd
>
<
1 kVA to 3000 kVA
(increments of 0.1 kVA)
X
X
Frequency
Frequency
>
<
45 Hz to 65 Hz
(increments of 0.01
Hz)
X
X
Quadrant
Operating quadrant 1
=
–
X
X
Operating quadrant 2
=
–
X
X
Operating quadrant 3
=
–
X
X
Operating quadrant 4
=
–
X
X
Field
Direct rotating field
=
–
X
X
Indirect rotating field
=
–
X
X
Lead or lag circuit
Capacitive circuit (lead)
=
–
X
X
Inductive circuit (lag)
=
–
X
X
3.4.7
Alarm log
The Energy trip unit has an internal memory to enable the following logs to be stored:
- Trip alarm log (up to 10 events)
- Custom alarm log (up to 40 events)
- Log of modifications to trip unit protection settings (up to 5 events per protection
parameter)
These logs are updated after each event.
Trip alarm log
Each trip event is saved with the following information:
- Trip cause
- Phase concerned by the fault (only for long time delay, short time delay and
instantaneous causes)
- Fault current value (only long time delay, short time delay, instantaneous and
ground causes)
- User time
- Machine time
Summary of Contents for h3+
Page 1: ...Moulded Case Circuit Breakers up to 250 A h3 Communication System manual...
Page 2: ...2 6LE005550A...
Page 4: ...4 6LE005550A...
Page 10: ......
Page 116: ...116 6LE005550A...
Page 124: ...124 6LE005550A...
Page 125: ...125 6LE005550A Support Page 6 1 Troubleshooting 126...
Page 127: ...127 6LE005550A...