
110
6LE005550A
Starting, commissioning, operation
4.7 Commissioning via the HTP610H configuration tool
4.7.3
Trip curve test via HTP610H
DANGER
Risk of serious injury or danger of death.
Ensure that the power supply inlet upstream of the circuit breaker is cut off and
isolated before performing a trip curve test.
The HTP610H configuration tool is used to test the trip curves on the h3+ LSnI, LSI,
LSIG and Energy circuit breakers.
The trip test is performed from the
Test
menu.
HTP610H tool test menu
Test parameter tab
Possible setting
Phase (pole to trip)
Phase - Neutral - Ground
Type
Automatic - Semi-automatic - Manual
PTA & Long time delay
(threshold values)
Activated - Deactivated
Strength
Choice of test current strength for a manual type test
Type of test
Result
Automatic
All of the points on the trip curve are tested
Semi-automatic
All of the points on the trip curve are tested in stepping mode.
Manual
The configuration tool tests the strength fixed on all the
threshold parameters chosen when adjusting the protection.
Summary of Contents for h3+
Page 1: ...Moulded Case Circuit Breakers up to 250 A h3 Communication System manual...
Page 2: ...2 6LE005550A...
Page 4: ...4 6LE005550A...
Page 10: ......
Page 116: ...116 6LE005550A...
Page 124: ...124 6LE005550A...
Page 125: ...125 6LE005550A Support Page 6 1 Troubleshooting 126...
Page 127: ...127 6LE005550A...