Starting, commissioning, operation
4.3 Connecting the communication module
4.3.1
Connecting the module to
the circuit breaker
The communication module is connected to the Energy circuit breaker using the CIP
adapter. The CIP adapter cable is composed of an RJ9 connector to connect to the
communication module and a suitable connector to connect to the CIP connector.
Adaptateur CIP
Communication module connection
Here is the procedure to follow to connect the communication module:
Action
Note/Illustration
1
Switch the Energy circuit
breaker to the OFF or
tripped position.
2
Open the front cover of the
circuit breaker.
The front cover of the circuit breaker can only be opened in the
OFF or tripped position.
3
Insert the CIP connector for
the CIP adapter in one of
the connectors marked CIP
inside the circuit breaker on
the left-hand side
Risk of damaging the CIP connector.
Respect the direction of insertion for the connector:
The adapter part marked CIP must be visible from the front.
Avoid forcing the connector when inserting.
4
Route the cable for the CIP
adapter along the left-hand
side cable channel of the
circuit breaker provided for
this purpose.
If necessary, use the side
support supplied with the
communication module to
connect the cable to the
side wall (see illustration
below).
Please respect the wiring rules in force in switchboards:
- Separate the routing of the power cables and the circulation
of low-level signal cables
- Secure the cable along the routing.
Summary of Contents for h3+
Page 1: ...Moulded Case Circuit Breakers up to 250 A h3 Communication System manual...
Page 2: ...2 6LE005550A...
Page 4: ...4 6LE005550A...
Page 10: ......
Page 116: ...116 6LE005550A...
Page 124: ...124 6LE005550A...
Page 125: ...125 6LE005550A Support Page 6 1 Troubleshooting 126...
Page 127: ...127 6LE005550A...