22
6LE005550A
Description of the h3+ communication system
2.4 HTD210H panel display
2.4.1
Presentation
The HTD210H panel display is an optional accessory which is used to configure the
Energy trip unit and display the data on a panel or door near the circuit breaker.
HTD210H panel display
It is easily mounted on a door or a panel of a board thanks to its minimal depth
behind the door.
Only an accessories cable is necessary to provide the connection with the Energy
circuit breaker (24 VDC supply included).
The front of the equipment is protected by a transparent and sealed wall in order to
obtain IP65 protection once installed in an appropriate distribution board.
The LCD screen is backlit to ensure it can be easily read even at low ambient light.
2.4.2
Characteristics of the
HTD210H display
Functions of the HTD210H panel display
The HTD210H display provides the following information:
- The circuit breaker protection parameters
- The variables measured by the circuit breaker
- The alarm management parameters
- The event logs
- The identification characteristics of the circuit breaker
It is used to define and modify the following data:
- Circuit breaker protection parameters
- Measurement parameters
- Output contact parameters
- Alarm management
Technical specifications
Dimensions
97 x 97 x 46 mm (27 mm behind the door)
Door cutout
92 x 92 mm
Screen dimensions
37 x 78 mm
Display
blue backlight
Alarm LED
flashing red
Communication LED
flashing yellow
Power supply LED
permanent green
Typical consumption
2 VA
Operating temperature
-10 °C…+55 °C
Category of use
III
Protection index
IP65 (rear IP20)
Rated operating voltage
24 VDC (+/- 30%)
Summary of Contents for h3+
Page 1: ...Moulded Case Circuit Breakers up to 250 A h3 Communication System manual...
Page 2: ...2 6LE005550A...
Page 4: ...4 6LE005550A...
Page 10: ......
Page 116: ...116 6LE005550A...
Page 124: ...124 6LE005550A...
Page 125: ...125 6LE005550A Support Page 6 1 Troubleshooting 126...
Page 127: ...127 6LE005550A...