Function of the Energy trip unit
3.3 Measurement function
3.3.6
Energy measurements
The Energy trip unit calculates the various energy levels by integrating the
instantaneous power over a network period.
The Energy trip unit supplies several energy counters which can count up to
4,294,967,295 kWh / kvarh / kVAh. All of these counters provide unsigned absolute
values except for the signed counters. They count the stored energy by increasing
incrementally every second.
The partial energy counters can be reset from the embedded display, the panel
display and the HTP610H configuration tool.
Partial energy counter
Symbol
Reset
Active energy delivered
Ea In,
X
Active energy received
Ea Out
X
Reactive energy delivered
Er In
X
Active energy received
Er Out
X
Absolute active energy
(del received)
Ea abs
X
Absolute reactive energy
(del received)
Er Abs
X
Signed active energy
Ea
X
Signed reactive energy
Er
X
Apparent energy
Es
X
Total energy
counter
Electrical variable
Reset
Active energy delivered
Ea In NR
No reset
Active energy received
Ea Out NR
No reset
Note
The ErIn, ErOut, Er Abs, Er, Es values depend on the arithmetic or vector addition
convention for reactive or apparent power (see configuration, see § 3.3.10).
3.3.7
Demand values (averaged
values over an interval)
The Energy trip unit calculates the averaged current and power values by integration
over a given time interval. These are the Demand values or the averaged values
over an interval. These values are useful in order to create a load profile for the
loads supplied by the Energy circuit breaker. They must not be confused with the
instantaneous averages (Instantaneous average current, etc.).
Calculation principle
The Energy trip unit calculates a value averaged (Demand value) out over an interval
using the electrical measurement G over a time interval T divided by this same
interval T.
The time interval T designates the configurable integration interval.
There are 3 types of integration interval:
- Fixed integration interval
- Sliding integration interval
Summary of Contents for h3+
Page 1: ...Moulded Case Circuit Breakers up to 250 A h3 Communication System manual...
Page 2: ...2 6LE005550A...
Page 4: ...4 6LE005550A...
Page 10: ......
Page 116: ...116 6LE005550A...
Page 124: ...124 6LE005550A...
Page 125: ...125 6LE005550A Support Page 6 1 Troubleshooting 126...
Page 127: ...127 6LE005550A...