Function of the Energy trip unit
3.4 Managing alarms and logs
Note
These system alarms can be assigned to the OAC output contact. In this case,
the OAC pop-up will be added to other pop-ups on the respective displays.
3.4.6
Configuring alarms
Configuring the PTA overload pre-alarm
The trip threshold and time delay for the PTA overload pre-alarm can be adjusted.
The parameters are defined in relation to the long time delay lr and tr parameters.
PTA threshold (% Ir)
PTA pre-alarm threshold
PTA time delay (% tr)
PTA pre-alarm time delay
PTA pre-alarm setting
Default setting
PTA threshold (% Ir)
60 to 95 (increments of 5%)
90
PTA time delay (% tr)
5 to 80 (increments of 5%)
50
Configuring the OAC output contact
The OAC output contact is set using two parameters.
- Alarm allocation
- Contact behaviour
OAC output setting
Default setting
Alarm allocation
See list.
PTA overload pre-alarm
Contact behaviour
Automatic - manual
Automatic
List of alarms available to assign to the OAC output contact:
Alarms available
PTA overload pre-alarm
Custom alarm
1
Custom alarm
2
Custom alarm
3
Custom alarm
4
Custom alarm
5
Custom alarm
6
Custom alarm
7
Custom alarm
8
Custom alarm
9
Custom alarm
10
Custom alarm
11
Custom alarm
12
Internal trip unit error
Trip unit temperature alarm
Rupture of the neutral pole
None
Contact behaviour
In
Automatic
mode, the OAC contact will open automatically 500 ms after the alarm
disappears.
In
Manual
mode, the OAC contact will remain active after the fault disappears until
the alarm is cleared via the embedded display.
Summary of Contents for h3+
Page 1: ...Moulded Case Circuit Breakers up to 250 A h3 Communication System manual...
Page 2: ...2 6LE005550A...
Page 4: ...4 6LE005550A...
Page 10: ......
Page 116: ...116 6LE005550A...
Page 124: ...124 6LE005550A...
Page 125: ...125 6LE005550A Support Page 6 1 Troubleshooting 126...
Page 127: ...127 6LE005550A...