108
6LE005550A
Starting, commissioning, operation
4.7 Commissioning via the HTP610H configuration tool
4.7.2
Configuration
recommendations via
HTP610H
Energy circuit breaker protection setting
Before attempting to set the Energy circuit breaker protection level with the
configuration tool, it is necessary to set the max Ir setpoint on the Energy trip unit.
Refer to § 4.2.3 page 81.
After having opened a circuit breaker management session, all the protection setting
parameters can be modified from the
Protection Settings
menu.
Note
Certain protection parameters may or may not be available depending on the
Energy circuit breaker model. In particular, the
ZSI
sub-menu is only available on an
Energy P250 and above circuit breaker.
Protection settings in the HTP610H tool
Setting the Energy circuit breaker measurement parameters via the HTP610H tool
The Energy circuit breaker measurement parameters can be modified from the
Measurement Settings
sub-menu.